Clean Room Differential Pressure Monitor
Feature
Applications:
Input | |
Sensors | Integrated Differential Pressure Sensor |
Communication | |
Communication | Isolated RS-485 communication with Modbus RTU Protocol |
Programmable parameter | 9600 bps, Parity, Data bits, Stop bits |
No. of salve ID | 1-250 |
Environmental | |
Operating Ambient Temp. | 0 to 50 Degree Centigrade |
Humidity | Below 90 Percent RH, Non condensing. |
Dimensions | |
Flush mounting plate | SS-304 |
Front plate size | 110 mm(W) x 90 mm(H) |
Back enclosure | 76 mm (W) x 70 mm(H) x 45 mm(D) MS with powder coated |
Mounting | Modular wall mounting with Stainless Steel Front |
Electrical | |
Supply voltage | 24 VDC +/-10 Percent |
Power consumption | Less than 1.2 watt at 24VDC |
Programmable Parameters | |
Set point | 2Nos. AL1, AL2 User Programmable |
Programming of parameters | 3 Nos. push button front keys (with password protection) |
Alarm logic | High or Low, user programmable |
Indication | |
Display | 4 digit Seven Segment 0.4 inch Red LED display for Differential Pressure Indication |
Status indication | 2 LEDs for Alarms Integrated Buzzer for process violation of Alarm limits. |
Range & Resolution
Range | Resolution |
(-100 to 100) mmWC | 0.1 |
(-10 to 10) cmWC | 0.1 |
(-7.5 to 7.5) mmHG | 0.1 |
(-1000 to 1000) Pascal | 1 |
(-10 to 10) Hectopascal | 0.1 |
NOTE : Other Differential Pressure Range/Unit, Available on request,contact to factory.
![]() |
AMBETRONICS ENGINEERS PVT. LTD.
All Rights Reserved.(Terms of Use) Developed and Managed by Infocom Network Private Limited. |